Specifications
ATEX execution | II 2G Ex db IIC T6...T1 Gb |
ATEX certificate | DEKRA 17ATEX0123 X |
IECEx execution | Ex db IIC T6...T1 Gb |
IECEx certificate | IECEx DEK 17.0046X |
Suitable for zone | 1 and 2 |
Ingress protection | IP66 / IEC529 |
Ambient temp. limits | -45°C...+80°C, this can be limited depending on the materials applied such as cables, connection heads, junction boxes and transmitters. |
Model and Type | To be specified |
Ambient temp. limits | Depending on transmitter specs. |
Material | Aluminium or Stainless steel 316 |
Cable entry | M20x1.5 standard, other threads possible. Two entries optional |
Cover | Threaded with retaining chain |
Fire Lock | At process side |
Construction | Springloaded and replaceable |
Springaction | >10mm standard, >40mm optional |
Diameter | 6.0mm standard, other diameters possible |
Type | Mineral insulated (MgO) |
Execution | Single or Duplex Pt100 |
Connection | 3-wire standard, 4-wire optional |
Accuracy | According IEC 60751 Cl. B, A or AA |
Measuring range | -20°C...+400°C standard, -220°C...+600°C optional |
Type | Nipple - union - nipple standard, other constructions possible |
Material | Stainless Steel |
Style / Connection | 1/2" NPT standard, other threads possible |
Length | 150mm standard, other lengths possible |
Customisation possibilities
You can remark the customisation in your quote
Productcode | LEX30 |
---|---|
Sensor S of D | … |
Connection 3- or 4-wire | … |
Class B, A or AA | … |
Diameter "D" in mm | … |
Length "U" in mm | … |
Length "X" in mm | … |
Transmitter model | To specify |